Table 278: EFIPTOC Group settings
Parameter Values (Range) Unit Step Default Description
Start value 1.00...40.00 xIn 0.01 1.00 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scaling the start value
Operate delay time 20...200000 ms 10 20 Operate delay time
Table 279: EFIPTOC Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Reset delay time 0...60000 ms 1 20 Reset delay time
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used Io signal
4.2.1.10 Monitored data
Table 280: EFLPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
EFLPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 281: EFHPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
EFHPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 282: EFIPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
EFIPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1YHT530004D05 D Section 4
Protection functions
615 series 271
Technical Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF615 L and is the answer not in the manual?

ABB REF615 L Specifications

General IconGeneral
TypeFeeder Protection Relay
Rated Frequency50/60 Hz
WeightApprox. 1.5 kg
Communication ProtocolsIEC 61850, Modbus RTU, DNP3
Protection FunctionsOvercurrent, Earth fault, Thermal overload, Under/Over voltage, Under/Over frequency
EnclosureIP20

Related product manuals