• CNT_SHOT3: counts reclose commands that are executed from shot 3
• CNT_SHOT4: counts reclose commands that are executed from shot 4
• CNT_SHOT5: counts reclose commands that are executed from shot 5
The counters are disabled through communication with the DsaCnt parameter.
When the counters are disabled, the values are not updated.
The counters are reset through communication with the RsCnt parameter.
9.4.6 Application
Modern electric power systems can deliver energy to users very reliably. However,
different kind of faults can occur. Protection relays play an important role in
detecting failures or abnormalities in the system. They detect faults and give
commands for corresponding circuit breakers to isolate the defective element
before excessive damage or a possible power system collapse occurs. A fast
isolation also limits the disturbances caused for the healthy parts of the power system.
The faults can be transient, semi-transient or permanent. Permanent fault, for
example in power cables, means that there is a physical damage in the fault
location that must first be located and repaired before the network voltage can be
restored.
In overhead lines, the insulating material between phase conductors is air. The
majority of the faults are flash-over arcing faults caused by lightning, for example.
Only a short interruption is needed for extinguishing the arc. These faults are
transient by nature.
A semi-transient fault can be caused for example by a bird or a tree branch falling
on the overhead line. The fault disappears on its own if the fault current burns the
branch or the wind blows it away.
Transient and semi-transient faults can be cleared by momentarily de-energizing
the power line. Using the auto-reclose function minimizes interruptions in the
power system service and brings the power back on-line quickly and effortlessly.
The basic idea of the auto-reclose function is simple. In overhead lines, where the
possibility of self-clearing faults is high, the auto-reclose function tries to restore
the power by reclosing the breaker. This is a method to get the power system back
into normal operation by removing the transient or semi-transient faults. Several
trials, that is, auto-reclose shots are allowed. If none of the trials is successful and
the fault persists, definite final tripping follows.
The auto-reclose function can be used with every circuit breaker that has the ability
for a reclosing sequence. In DARREC auto-reclose function the implementing
method of auto-reclose sequences is patented by ABB
1YHT530004D05 D Section 9
Control functions