Parameter Values (Range) Unit Step Default Description
Pol reversal 0=False
1=True
0=False Rotate polarizing quantity
Curve parameter A 0.0086...120.0000 28.2000 Parameter A for customer programmable
curve
Curve parameter B 0.0000...0.7120 0.1217 Parameter B for customer programmable
curve
Curve parameter C 0.02...2.00 2.00 Parameter C for customer
programmable curve
Curve parameter D 0.46...30.00 29.10 Parameter D for customer
programmable curve
Curve parameter E 0.0...1.0 1.0 Parameter E for customer programmable
curve
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used Io signal
Pol signal Sel 1=Measured Uo
2=Calculated Uo
3=Neg. seq. volt.
1=Measured Uo Selection for used polarization signal
4.2.2.12 Monitored data
Table 304: DEFLPDEF Monitored data
Name
Type Values (Range) Unit Description
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operating
angle and characteristic
angle
ANGLE FLOAT32 -180.00...180.00 deg Angle between
polarizing and operating
quantity
I_OPER FLOAT32 0.00...40.00 Calculated operating
current
DEFLPDEF Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1YHT530004D05 D Section 4
Protection functions
615 series 301
Technical Manual