Table 142: Truth table for CONTROL
Input Output
CTRL_OFF CTRL_LOC
CTRL_STA
1)
CTRL_REM
TRUE any any any OFF = TRUE
FALSE TRUE any any LOCAL = TRUE
FALSE FALSE TRUE any STATION =
TRUE
FALSE FALSE FALSE TRUE REMOTE = TRUE
FALSE FALSE FALSE FALSE OFF = TRUE
1) If station authority is not in use, the CTRL_STA input is interpreted as CTRL_REM.
The station authority check based on the IEC 61850 command originator category
in control command can be enabled by setting the value of the Station authority
setting to "Station, Remote" (The command originator validation is performed only
if the LR control setting is set to "Binary input"). The station authority check is not
in use by default.
3.14.8.3 Signals
Table 143: CONTROL input signals
Name
Type Default Description
CTRL_OFF
BOOLEAN 0 Control input OFF
CTRL_LOC
BOOLEAN 0 Control input Local
CTRL_STA
BOOLEAN 0 Control input Station
CTRL_REM
BOOLEAN 0 Control input Remote
Table 144: CONTROL output signals
Name
Type Description
OFF BOOLEAN Control output OFF
LOCAL BOOLEAN Control output Local
STATION BOOLEAN Control output Station
REMOTE BOOLEAN Control output Remote
1YHT530004D05 D Section 3
Basic functions
615 series 131
Technical Manual