4.5 Voltage protection
4.5.1 Three-phase overvoltage protection PHPTOV
4.5.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase overvoltage protection PHPTOV 3U> 59
4.5.1.2 Function block
GUID-871D07D7-B690-48FD-8EA1-73A7169AE8BD V1 EN
Figure 248: Function block
4.5.1.3 Functionality
The three-phase overvoltage protection PHPTOV is applied on power system
elements, such as generators, transformers, motors and power lines, to protect the
system from excessive voltages that could damage the insulation and cause
insulation breakdown. The three-phase overvoltage function includes a settable
value for the detection of overvoltage either in a single phase, two phases or three
phases.
PHPTOV includes both definite time (DT) and inverse definite minimum time
(IDMT) characteristics for the delay of the trip.
The function contains a blocking functionality. It is possible to block function
outputs, timer or the function itself, if desired.
4.5.1.4 Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of the three-phase overvoltage protection can be described using a
module diagram. All the modules in the diagram are explained in the next sections.