4.3.1.9 Monitored Data
Table 336: LNPLDF Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
I_AMPL_LOC_A FLOAT32 0.00...40.00 xIr Local phase A amplitude
after correction
I_AMPL_LOC_B FLOAT32 0.00...40.00 xIr Local phase B amplitude
after correction
I_AMPL_LOC_C FLOAT32 0.00...40.00 xIr Local phase C amplitude
after correction
I_AMPL_REM_A FLOAT32 0.00...40.00 xIr Remote phase A
amplitude after correction
I_AMPL_REM_B FLOAT32 0.00...40.00 xIr Remote phase B
amplitude after correction
I_AMPL_REM_C FLOAT32 0.00...40.00 xIr Remote phase C
amplitude after correction
ID_A FLOAT32 0.00...80.00 xIr Differential current
phase A
ID_B FLOAT32 0.00...80.00 xIr Differential current
phase B
ID_C FLOAT32 0.00...80.00 xIr Differential current
phase C
IB_A FLOAT32 0.00...80.00 xIr Stabilization current
phase A
IB_B FLOAT32 0.00...80.00 xIr Stabilization current
phase B
IB_C FLOAT32 0.00...80.00 xIr Stabilization current
phase C
I_ANGL_DIFF_A FLOAT32 -180.00...180.00 deg Current phase angle
differential between local
and remote, phase A
I_ANGL_DIFF_B FLOAT32 -180.00...180.00 deg Current phase angle
differential between local
and remote, phase B
I_ANGL_DIFF_C FLOAT32 -180.00...180.00 deg Current phase angle
differential between local
and remote, phase C
LNPLDF Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 4 1YHT530004D05 D
Protection functions
382 615 series
Technical Manual