For further information on warning indications, see the operation manual.
3.3 LED indication control
The IED includes a global conditioning function LEDPTRC that is used with the
protection indication LEDs.
LED indication control should never be used for tripping purposes.
There is a separate trip logic function TRPPTRC available in the
IED configuration.
LED indication control is preconfigured in a such way that all the protection
function general start and operate signals are combined with this function
(available as output signals OUT_START and OUT_OPERATE). These signals are
always internally connected to Start and Trip LEDs. LEDPTRC collects and
combines phase information from different protection functions (available as
output signals OUT_ST_A /_B /_C and OUT_OPR_A /_B /_C). There is
also combined earth fault information collected from all the earth fault functions
available in the IED configuration (available as output signals OUT_ST_NEUT and
OUT_OPR_NEUT).
3.4 Programmable LEDs
3.4.1 Function block
GUID-00339108-34E4-496C-9142-5DC69F55EE7A V1 EN
Figure 8: Function block
3.4.2 Functionality
The programmable LEDs reside on the right side of the display on the LHMI.
1YHT530004D05 D Section 3
Basic functions
615 series 63
Technical Manual