Many applications require several steps using different current start levels and time
delays. EFxPTOC consists of three different protection stages.
Low EFLPTOC
High EFHPTOC
Instantaneous EFIPTOC
EFLPTOC contains several types of time-delay characteristics. EFHPTOC and
EFIPTOC are used for fast clearance of serious earth faults.
4.2.1.8 Signals
Table 268: EFLPTOC Input signals
Name Type Default Description
Io SIGNAL 0 Residual current
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
ENA_MULT BOOLEAN 0=False Enable signal for current multiplier
Table 269: EFHPTOC Input signals
Name
Type Default Description
Io SIGNAL 0 Residual current
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
ENA_MULT BOOLEAN 0=False Enable signal for current multiplier
Table 270: EFIPTOC Input signals
Name
Type Default Description
Io SIGNAL 0 Residual current
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
ENA_MULT BOOLEAN 0=False Enable signal for current multiplier
Table 271: EFLPTOC Output signals
Name
Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
Table 272: EFHPTOC Output signals
Name
Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
Section 4 1YHT530004D05 D
Protection functions
268 615 series
Technical Manual