EasyManua.ls Logo

ABB REF615 L - The Measuring Configuration

ABB REF615 L
896 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
At internal fault, the secondary circuit voltage can easily exceed the isolation
voltage of the CTs, connection wires and IED. To limit this voltage, a voltage-
dependent resistor VDR is used as shown in Figure 234.
The whole scheme, that is, the stabilizing resistor, voltage-dependent resistor and
wiring, must be adequately maintained (operation- and insulation-tested regularly)
to be able to withstand the high-voltage pulses which appear during an internal
fault throughout the lifetime of the equipment. Otherwise, during a fault within the
zone of protection, any flashover in the CT secondary circuits or in any other part
of the scheme may prevent a correct operation of the high-impedance differential
function.
4.3.4.6 The measuring configuration
The external measuring configuration is composed of four current transformers
measuring the currents and a stabilizing resistor. A varistor is needed if high
overvoltages are expected.
The value of the stabilizing resistor is calculated with the formula:
R
U
I
s
s
rs
=
GUID-00FCABE9-93E2-4BDD-83C6-EB1BE7FFE986 V1 EN (Equation 58)
R
s
the resistance of the stabilizing resistor
U
s
the stabilizing voltage of the IED
I
rs
the value of the
Low operate value
setting
The stabilizing voltage is calculated with the formula:
U
I
n
R R
s
k
in m
= +
max
( )
GUID-6A4C58E7-3D26-40C9-A070-0D99BA209B1A V1 EN (Equation 59)
I
kmax
the highest through-fault current
n the turns ratio of the CT
R
in
the secondary internal resistance of the CT
R
m
the resistance of the longest loop of secondary circuit
Additionally, it is required that the current transformers' knee-point voltages U
k
are
at least twice the stabilizing voltage value U
s
.
Section 4 1YHT530004D05 D
Protection functions
436 615 series
Technical Manual

Table of Contents

Related product manuals