5.6.7 Settings
Table 489: CBRSOF Group settings
Parameter Values (Range) Unit Step Default Description
SOTF reset time 0...60000 ms 1 1000 SOTF detection period after initialization
Operate delay time 0...60000 ms 1 0 Time delay for start input
Table 490: CBRSOF Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
5.6.8 Monitored data
Table 491: CBRSOF Monitored data
Name Type Values (Range) Unit Description
CBRSOF Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.7 Uncorresponding position startup UPSCBR
5.7.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Uncorresponding position startup UPSCBR UPSS UPSM
5.7.2 Function block
GUID-9ECE8940-32C4-46F7-84E7-CB129B93B080-CN V2 EN
Figure 301: Function block
Section 5 1YHT530004D05 D
Protection related functions
566 615 series
Technical Manual