Table 221: DPH3LPDOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
OPR_A BOOLEAN Operate phase A
OPR_B BOOLEAN Operate phase B
OPR_C BOOLEAN Operate phase C
ST_A BOOLEAN Start phase A
ST_B BOOLEAN Start phase B
ST_C BOOLEAN Start phase C
Table 222: DPH3HPDOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
OPR_A BOOLEAN Operate phase A
OPR_B BOOLEAN Operate phase B
OPR_C BOOLEAN Operate phase C
ST_A BOOLEAN Start phase A
ST_B BOOLEAN Start phase B
ST_C BOOLEAN Start phase C
4.1.4.9  Settings
Table 223: DPH3LPDOC Group settings
Parameter
Values (Range) Unit Step Default Description
Start value 0.05...5.00 xIn 0.01 0.05 Start value
Start value Mult 0.8...10.0   0.1 1.0 Multiplier for scaling the start value
Time multiplier 0.05...15.00   0.05 1.00 Time multiplier in IEC/ANSI IDMT curves
Operate delay time 40...200000 ms 10 40 Operate delay time
Table continues on next page
Section 4 1YHT530004D05 D
Protection functions
220 615 series