3.12.8.3 Signals
Table 73: GOOSERCV_INT32 Input signals
Name Type Default Description
IN INT32 0 Input signal
Table 74: GOOSERCV_INT32 Output signals
Name Type Description
OUT INT32 Output signal
VALID BOOLEAN Output signal
3.13 Type conversion function blocks
3.13.1 QTY_GOOD function block
3.13.1.1 Function block
GUID-1999D6D9-4517-4FFE-A14D-08FDB5E8B9F6 V1 EN
Figure 38: Function block
3.13.1.2 Functionality
The QTY_GOOD function block evaluates the quality bits of the input signal and
passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function
output, binary input, application function output or received GOOSE signal). Due
to application logic quality bit propagation, each (simple and even combined)
signal has quality which can be evaluated.
The OUT output indicates quality good of the input signal. Input signals that have
no quality bits set or only test bit is set, will indicate quality good status.
3.13.1.3 Signals
Table 75: QTY_GOOD Input signals
Name
Type Default Description
IN Any 0 Input signal
1YHT530004D05 D Section 3
Basic functions
615 series 103