The start value multiplication is normally done when the inrush detection function
(INRPHAR) is connected to the ENA_MULT input.
A070554 V1 EN
Figure 102: Start value behavior with the 
ENA_MULT
 input activated
Phase selection logic
The phase selection logic detects the faulty phase or phases and controls the timers
according to the set value of the Num of start phases setting.