LV side (A): I
nT_B
= 5 MVA / (1.732 × 10.5 kV) = 274.9 A
So the settings for CT ratio Corrections at HV (A) and LV (B) side are:
CT ratio Correction (A) = 200 A / 144.3 A = 1.386
CT ratio Correction (B) = 300 A / 274.9 A = 1.091
CT connections
The connections of the primary current transformers are designated as “Type 1”
and “Type 2”.
If the positive directions of the winding 1 and winding 2 IED currents are
opposite, the CT connection type setting parameter is “Type 1”. The
connection examples of “Type 1” are as shown in the Figure 185 and Figure
186.
If the positive directions of the winding 1 and winding 2 IED currents equate,
the CT connection type setting parameter is “Type 2”. The connection
examples of “Type 2” are as shown in the
Figure 187 and Figure 188.
The default value of the CT connection type setting is “Type 1”.
Section 4 1YHT530004D05 D
Protection functions