differential current. The elimination of the zero-sequence component can be
selected for that winding by setting the Zro A elimination parameter.
Table 339: TR2PTDF settings corresponding to the power transformer vector groups and zero-
sequence elimination
Vector group of the
transformer
Winding 1 type Winding 2 type Clock number Zro A Elimination
Yy0 Y y Clk Num 0 Not needed
YNy0 YN y Clk Num 0 HV side
YNyn0 YN yn Clk Num 0 HV & LV side
Yyn0 Y yn Clk Num 0 LV side
Yy2 Y y Clk Num 2 Not needed
YNy2 YN y Clk Num 2 Not needed
YNyn2 YN yn Clk Num 2 Not needed
Yyn2 Y yn Clk Num 2 Not needed
Yy4 Y y Clk Num 4 Not needed
YNy4 YN y Clk Num 4 Not needed
YNyn4 YN yn Clk Num 4 Not needed
Yyn4 Y yn Clk Num 4 Not needed
Yy6 Y y Clk Num 6 Not needed
YNy6 YN y Clk Num 6 HV side
YNyn6 YN yn Clk Num 6 HV & LV side
Yyn6 Y yn Clk Num 6 LV side
Yy8 Y y Clk Num 8 Not needed
YNy8 YN y Clk Num 8 Not needed
YNyn8 YN yn Clk Num 8 Not needed
Yyn8 Y yn Clk Num 8 Not needed
Yy10 Y y Clk Num 10 Not needed
YNy10 YN y Clk Num 10 Not needed
YNyn10 YN yn Clk Num 10 Not needed
Yyn10 Y yn Clk Num 10 Not needed
Yd1 Y d Clk Num 1 Not needed
YNd1 YN d Clk Num 1 Not needed
Yd5 Y d Clk Num 5 Not needed
YNd5 YN d Clk Num 5 Not needed
Yd7 Y d Clk Num 7 Not needed
YNd7 YN d Clk Num 7 Not needed
Yd11 Y d Clk Num 11 Not needed
YNd11 YN d Clk Num 11 Not needed
Dd0 D d Clk Num 0 Not needed
Dd2 D d Clk Num 2 Not needed
Dd4 D d Clk Num 4 Not needed
Table continues on next page
1YHT530004D05 D Section 4
Protection functions
615 series 403
Technical Manual