Name Type Default Description
BLK_CLOSE BOOLEAN 0=False Blocks closing
ITL_BYPASS BOOLEAN 0=False Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
EXE_OP BOOLEAN 0=False Executes the command for open direction
EXE_CL BOOLEAN 0=False Executes the command for close direction
OPENPOS BOOLEAN 0=False Apparatus open position
CLOSEPOS BOOLEAN 0=False Apparatus closed position
Table 590: ESXSWI Input signals
Name Type Default Description
ENA_OPEN BOOLEAN 1=True Enables opening
ENA_CLOSE BOOLEAN 1=True Enables closing
BLK_OPEN BOOLEAN 0=False Blocks opening
BLK_CLOSE BOOLEAN 0=False Blocks closing
ITL_BYPASS BOOLEAN 0=False Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
EXE_OP BOOLEAN 0=False Executes the command for open direction
EXE_CL BOOLEAN 0=False Executes the command for close direction
OPENPOS BOOLEAN 0=False Apparatus open position
CLOSEPOS BOOLEAN 0=False Apparatus closed position
Table 591: CBXCBR Output signals
Name
Type Description
SELECTED BOOLEAN Object selected
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
OKPOS BOOLEAN Apparatus position is ok
OPEN_ENAD BOOLEAN Opening is enabled based on the input status
CLOSE_ENAD BOOLEAN Closing is enabled based on the input status
Table 592: DCXSWI Output signals
Name
Type Description
SELECTED BOOLEAN Object selected
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
Table continues on next page
1YHT530004D05 D Section 9
Control functions
615 series 673