Section 12 – Power Requirements
12-11
3.
In table 6, enter devices connected to Auxiliary Relay (if used for wet operation). Calculate standby
and alarm currents, then add to get Auxiliary Relay current subtotal.
Table 6: AUXILIARY RELAY CURRENT LOAD
Total Current
Device Model # Device Current X # of Units = Standby Alarm
Auxiliary Relay Subtotal
(terminal 10)1.7 amp max
(If setup for wet operation)
4.
In table 7, enter devices connected to Bell 1 output. Calculate alarm currents, then add to get Bell
1 output current subtotal.
Table 7: BELL 1 OUTPUT CURRENT LOAD
Total Current
Device Model # Device Current X # of Units = Standby Alarm
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
Bell 1 Output Subtotal
(terminals 5 & 6) 1.7 amp max