FOCUS 200 PLUS Installation and Setup Guide
21-2
Installation Criteria
Control Unit
Current Draw
Standby 300mA
Alarm 440mA
Temperature Range 32°F (0°C) to 120°F (49°C)
Dimensions 18" H x 14-1/2" W x 4.3" D
Maximum Cable Runs
RS-485 Bus #1 4000 Feet
RS-485 Bus #2 4000 Feet
SIM Gateway Trunk 1000 Feet
PID Gateway Trunk (TB2 plus TB3) 1000 Feet
Branch Cable for PID and SIM Sensors 100 Feet
Note:
RS-485 bus and gateway trunk cable lengths may be less, depending on current loading and
voltage drop considerations.
SIM Gateway
Dimensions with Micro PID Housing 3-1/2" H x 3-1/2" W x 1-5/8" D (8.6cm x 8.6cm x 4cm)
Temperature Range 32°F (0°C) to 120°F (49°C)
Length of SIM Gateway Trunk 1000 feet (max.)
Gateway Circuit Power Requirement 50ma
Worst Case Voltage @ SIM Gateway 12.lVDC
(End of Standby Period) (8.4VDC)
Worst Case Voltage @ SIM Sensor 12.0VDC
(End of Standby Period) (8.3VDC)
SIM Resistor 33k 5% 1/2w
PID Gateway
Dimensions with Standard PID Housing 9-1/4" H x 5" W x 1-5/8" D (23.5cm x l2.7cm x 4.1cm)
Temperature Range 32°F (0°C) to 120°F (49°C)
Length of PID Gateway Trunk (TB2 plus TB3) 1000 Feet (max.)
Gateway Circuit Power Requirement 50mA
Minimum Voltage to PID Gateway 12.lVDC
(End of Standby Period) 8.5VDC
Voltage to Farthest PID on Gateway Trunk 12.1VDC (minimum)
(End of Standby Period) 8.5VDC
Worst Case Voltage to Sensor 11.6VDC
(End of Standby Period) 8.0VDC
Sensor Current from PID Standard PID 85mA maximum (current limited)
Maximum PID Loop Resistance 900 ohms
PID Supervisory Current 3mA
PID End-of-Line Resistor 3,010 ohms, 1%, 1/2W
PID Loop Off-Normal Retard 500mSec.
Note:
With AC power off and the battery fully charged the voltage to a sensor being powered by the
system must be greater than the rated minimal voltage of the sensor.

Table of Contents

Other manuals for ADT Focus 200 Plus

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ADT Focus 200 Plus and is the answer not in the manual?

ADT Focus 200 Plus Specifications

General IconGeneral
BrandADT
ModelFocus 200 Plus
CategorySecurity System
LanguageEnglish

Related product manuals