Rockwell Automation Publication 750-IN001P-EN-P - April 2017 201
Power Wiring Chapter 4
Table 33 - 480V, 60 Hz Input – Code P3 Thermal Magnetic Circuit Breaker Options
Table 34 - 480V, 60 Hz Input – Code P5 Molded Case Disconnect Switch Options (only floor
mount Frame 8)
Hp Amps Duty Line Side Terminal
Lugs
Terminal Size Recommended Torque
N•m (lb•in)
300 370 Heavy
140G-M-TLA23 (2) 250…500 MCM kit of 3 31 (274)
350
430 Normal
414 Heavy
454 Heavy
400
485 Light
140G-N-TLA43 (4) 4/0…500 MCM 43 (381)
485 Normal
485 Heavy
450
545 Light
545 Normal
545 Heavy
500
590 Light
617 Normal
617 Heavy
600
710 Light
710 Normal
650
765 Light
740 Normal
700 800 Light
Hp Amps Duty Line Side Terminal
Lugs
Terminal Size Recommended Torque
N•m (lb•in)
300 370 Heavy
140G-M-TLA23 (2) 250…500 MCM kit of 3 31 (274)
350
430 Normal
414 Heavy
454 Heavy
400
485 Light
485 Normal
485 Heavy
450
545 Light
545 Normal
545 Heavy
500
590 Light
617 Normal
617 Heavy
600
710 Light
140G-N-TLA43 (4) 4/0…500 MCM 43 (381)
710 Normal
650
765 Light
740 Normal
700 800 Light