Configuration Mode (ConF)
203
Current limiting mode
Ascend command
t
Reference
HSP
FrS
SCL
0
t
Frequency
HSP
FrS
SCL
0
Limit imposed
by current
limitation
t
Current
CLO
t
SCL: Adjustable s peed thres hold, above which current lim itation is active
CLO: Current lim itation for high-s peed function
Note:
The speed reached for a s pecific current will be lower in cas e of network undervoltage in com parison
with nom inal network voltage.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FUN- > HSH-