Configuration Mode (ConF)
DC Bus
Code Nam e / De s cription Adjustment range Factory s e tting
dCCM
[DC-Bus chaining]
[No]
(nO)
DC Bus chaining configuration
nO
[No]
(nO): Not assigned
[Bus & Main
]
(MAIn):
The drive is supplied by both DC Bus and supply mains.
[Only Bus ]
(bUS): The drive is supplied by DC Bus only.
DANGER
GROUND FAULT MONITORING DISABLED, NO ERROR DETECTION
Setting this param eter to
[Bus & M ain
]
(Main)
deactivates ground fault m onitoring.
•
Only use this parameter after a thorough risk assessment in com pliance with all regulations and s tandards
that apply to the device and to the application.
•
Im plem ent alternative ground fault m onitoring functions that do not trigger automatic error responses of the
drive, but allow for adequate, equivalent res ponses by other m eans in com pliance with all applicable
regulations and standards as well as the ris k as sessment.
•
Com m ission and tes t the sys tem with ground fault m onitoring enabled.
•
During com m issioning, verify that the drive and the sys tem operate as intended by perform ing tes ts and
sim ulations in a controlled environment under controlled conditions.
Failure to follow these instructions will result in death or serious injury.
dCCC
[DC-Bus compat.]
[Alti var] (AtU)
DC Bus chaining compatibility
AtU
Visible if
[DC-Bus chaining]
(dCCM) above is not set to
[No]
(nO).
[Altivar]
(AtU): Only ER24 drives are on the DC Bus chain.
[Le xium]
(LHM): At least one Lexium 32 drive is on the DC Bus chain.
-
For ER24-…K / /B, not depending on
[DC-Bus com pat.]
(dCCC) the parameters
[M ains voltage ]
(UrES),
[Unde rvoltage
level]
(
USL
),
[Brak ing
level]
(
Ub
r
)
are
forced
to
their
default
value.
-
For ER24-…/4K/B, if
[DC-Bus com pat.]
(dCCC) is set to
[Altivar]
(AtU) the parameters
[M ains voltage ]
(UrES),
[Unde rvoltage le ve l]
(USL),
[Brak ing leve l]
(Ubr) are forced to their default value.
For ER24-…/4K/B if
[DC-Bus com pat.]
(dCCC)
is set to
[Le xium ]
(LHM) the parameters
[M ains voltage ]
(UrES),
[Unde rv olt a g e
level]
(
USL
)
are
forced
to
their
default
value,
[Brak ing
level]
(
Ub
r
)
is
forced
to
780
Vdc
and
the
drive
will
trigger in
[Ove rbrak ing]
(ObF) at a DC Bus level of 820 Vdc instead of 880 Vdc to be compatible w ith Lexium 32 drives.
*
IPL
[Input phase loss]
Drive behaviour in case of input phase loss detected fault.
According to drive
rating.
*
Cannot be accessed if drive rating is
Visible if
[3.1 ACCESS LEVEL]
(LAC) is set to
[Expe rt]
(Epr)
and
[DC-Bus chaining]
(dCCM) above is set to
[No]
(nO).
[Ignore]
(nO): Detected fault ignored
[Freewheel]
(YES): Detected fault w ith freewheel stop
[Input phas e loss]
(IPL)
is forced to
[Ignore ]
(nO) if
[DC-Bus chaining]
(dCCM) above is set to
[Only Bus ]
(bUS).
See
[Input phas e loss]
(IPL)
in the Programming Manual (DRI- > CONF > FULL > FLT- > IPL-).
nO
Parameters described in this page can be accessed