Model 190 Installation, Technical and Operation
8400-M022-O1 Rev J
Page 170
18.2 Onboard Status/Diagnostic LED’s
The 190-DAC option card contains four (4) LED’s indicate run time
status and errors to the user.
LED
Indication
Description
D1
DC/DC Power
Voltage is in tolerance 9V ± 5% and
isolated DAC is powered. NOTE:
The DC/DC Power (D1) LED will be
on continuously when the DAC is
powered.
D2
Fault
IOUT Fault Current loop is open
circuit or insufficient
power supply voltage to
drive load.
Over Temp DAC core temperature
has exceeded limit.
D3
Sample
Blinks each time Sample is received
D4
Mainline
Heartbeat monitor that blinks each
time through main line routine
D4
D3
D2
D1
P1
P3
J2
J1
1
2
3
4
5

Table of Contents