DLP-G765 Install Air Plenum for ONS 15454 M2 Shelf in ETSI Configuration
This task installs the air plenum for the ONS 15454 M2 shelf in the ETSI configuration.Purpose
#2 Phillips Dynamometric screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Screws: M6.0 x 20 pan-head Phillips screws (4)
Wing head screws (4)
Adapter plates
One air plenum kit (horizontal and vertical air plenum)
Tools/Equipment
As neededRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
Procedure
Step 1 Install the ETSI adapter plates on the horizontal air plenum.
Step 2 Align the screws to fix the adapter plates to the horizontal air plenum. Insert the screws and tighten them to
a torque value of 11.5 in-lb (1.3 N-m) as shown in the following figure.
Cisco ONS 15454 Hardware Installation Guide
191
Installing the ONS 15454 M2 Shelf
DLP-G765 Install Air Plenum for ONS 15454 M2 Shelf in ETSI Configuration