Open-end wrench
Pinned hex (Allen) key
Tools/Equipment
NTP-G306 Install the ONS 15454 Shelf, on page 31Prerequisite Procedures
RequiredRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
Procedure
Step 1 Complete the DLP-G9 Open the Front Cabinet Compartment (Door) , on page 57.
Step 2 Complete the DLP-G10 Remove the Front Door , on page 58.
Step 3 If you are using an ETSI shelf, continue with the NTP-G4 Open and Remove the FMEC Cover (ETSI Only),
on page 60. If you are using an ANSI shelf, continue with the NTP-G5 Remove the Backplane Covers (ANSI
Only), on page 63.
Stop. You have completed this procedure.
DLP-G9 Open the Front Cabinet Compartment (Door)
This task opens the front door.Purpose
Pinned hex (Allen) keyTools/Equipment
NTP-G306 Install the ONS 15454 Shelf, on page 31Prerequisite Procedures
RequiredRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
The ONS 15454 shelf has an ESD plug input and is shipped with an ESD wrist strap. The ESD plug input is
located on the outside of the shelf on the right side. It is labeled “ESD” on the top and bottom. Always wear
an ESD wrist strap and connect the strap to the ESD plug when working on the ONS 15454. For detailed
instructions on how to wear the ESD wristband, refer to the Electrostatic Discharge and Grounding Guide for
Cisco CPT and Cisco ONS Platforms.
Note
Cisco ONS 15454 Hardware Installation Guide
57
Installing the ONS 15454 M12 (ANSI and ETSI) Shelf
DLP-G9 Open the Front Cabinet Compartment (Door)