• NTP-G10 Attach Wires to Alarm, Timing, LAN, and Craft Pin Connections , on page 100
• NTP-G11 Install an External Wire-Wrap Panel on the AEP (ANSI Only), on page 112
• NTP-G12 Install and Close the FMEC Cover (ETSI Only), on page 117
• NTP-G13 Install the Rear Cover (ANSI Only), on page 118
• Typical DWDM Rack Layouts, on page 120
• NTP-G14 Install DWDM Equipment, on page 123
• Multishelf Management, on page 137
• NTP-G301 Connect the ONS 15454 Multishelf Node and Subtending Shelves to an MS-ISC-100T Card,
on page 138
• NTP-G304 Configure the MS-ISC-100T Card for a ONS 15454 Multishelf Node for Non-Default Public
and Private VLAN IDs, on page 141
• NTP-G307 Perform the ONS 15454 Shelf Installation Acceptance Test , on page 143
• NTP-G295 Connect the ONS 15454 Multishelf Node and Subtending Shelves to a Catalyst 2950 or
Catalyst 3560, on page 146
• NTP-G296 Upgrade the ONS 15454 Multishelf with MS-ISC Card Configuration Using the Catalyst
3560, on page 148
• NTP-G297 Upgrade the ONS 15454 Multishelf with Catalyst 2950 Configuration Using the Catalyst
3560, on page 150
• NTP-G298 Configure a Cisco Catalyst 2950 or Catalyst 3560 (Active and Standby) for a ONS 15454
Multishelf Node, on page 152
• Ethernet Adapter Panel, on page 154
• Filler and Blank Cards, on page 156
• Cable Routing and Management, on page 157
ONS 15454 ANSI Rack Installation
The ONS 15454 ANSI shelf is mounted in a 19- or 23-in. (482.6- or 584.2-mm) equipment rack. The shelf
projects five inches (127 mm) from the front of the rack. It mounts in both Electronic Industries Alliance
(EIA) standard and Telcordia-standard racks. The shelf is a total of 17 inches (431.8 mm) wide with no
mounting ears attached. Ring runs are not provided by Cisco and might hinder side-by-side installation of
shelves where space is limited.
The ONS 15454 ANSI assembly measures 18.5 inches (469.9 mm) high, 19 or 23 inches (482.6 or 584.2 mm)
wide (depending on which way the mounting ears are attached), and 12 inches (304.8 mm) deep. You can
install up to four ONS 15454 ANSIs in a seven-foot (2133.6 mm) equipment rack. The ONS 15454 ANSI
must have one inch (25.4 mm) of airspace below the installed shelf to allow air flow to the fan intake. If a
second ONS 15454 ANSI is installed underneath the shelf, the air ramp on top of the lower shelf provides the
air spacing needed and should not be modified in any way. The following figure shows the dimensions of the
ONS 15454 ANSI.
A 10-Gbps-compatible shelf (15454-SA-ANSI or 15454-SA-HD) and fan-tray assembly (15454-FTA3,
15454-FTA3-T, or 15454-CC-FTA) are required if ONS 15454 ANSI 10-Gbps Cross-Connect (XC10G) cards
are installed in the shelf.
Note
Cisco ONS 15454 Hardware Installation Guide
24
Installing the ONS 15454 M12 (ANSI and ETSI) Shelf
ONS 15454 ANSI Rack Installation