NTP-G271 Install the Power and Ground to the ONS 15454 M2 Shelf
This procedure installs power feeds and grounds the ONS 15454 M2 system.Purpose
ANSI and ETSI:
#2 Phillips Dynamometric screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Screws
Ground cable 13.3-mm² (#6 AWG) stranded
Listed pressure dual-holes lugs suitable for #6 AWG copper conductors
Wire cutters
Wire strippers
Crimp tool
Fuse panel
ANSI only:
Power cable (from fuse panel to assembly), #12 AWG, copper conductors,
194 degrees F [90 degrees C])
Wire wrapper
Two-hole grounding lug, shipped with the ONS 15454 M2
ETSI only:
Power cable (from fuse panel to power modules), shipped with the ONS
15454 M2 ETSI
Two-hole grounding lug, shipped with the ONS 15454 M2
Tools/Equipment
NTP-G267 Install the Power Module in the ONS 15454 M2 Shelf, on page
230.
Connect the chassis to the office ground. For detailed instructions on how
to ground the chassis, refer to the Electrostatic Discharge and Grounding
Guide for Cisco CPT and Cisco ONS Platforms.
Prerequisite Procedures
RequiredRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
To ensure safety of personnel and equipment, do not connect any power cables into the power module
until the module is completely installed into the chassis. Statement 389
Warning
To reduce the risk of electric shock, switch on the power only after the power cord is completely installed
into the power module. Statement 390
Warning
Cisco ONS 15454 Hardware Installation Guide
239
Installing the ONS 15454 M2 Shelf
NTP-G271 Install the Power and Ground to the ONS 15454 M2 Shelf