Figure 130: Mounting an ONS 15454 M2 in a Rack
Step 3 Lift the shelf to the desired position in the rack.
To ensure proper cooling of the ONS 15454 M2 shelf, make sure that the space in front of the air
flow vents are free of cables, fibers, and mechanical fixtures for fiber and cable management.
Note
Step 4 Align the screw holes on the mounting brackets with the mounting holes in the rack.
Step 5 Using the Phillips Dynamometric screwdriver, install one mounting screw in each side of the assembly.
Tighten the screw to a torque value of 22 in-lb (2.5 N-m).
Step 6 When the shelf is secured to the rack, install the remaining two mounting screws on either sides of the shelf.
Step 7 Return to your originating procedure (NTP).
DLP-G590 Mount the ONS 15454 M2 Shelf on the Wall
This task explains how to mount the ONS 15454 M2 shelf on the wall.Purpose
• # 2 Phillips Dynamometric screwdriver
• 6 pan-head Phillips mounting screws
Tools/Equipment
NTP-G305 Unpack and Inspect the ONS 15454, ONS 15454 M2, and ONS 15454
M6 Shelves, on page 20.
Prerequisite Procedures
As neededRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
Cisco ONS 15454 Hardware Installation Guide
211
Installing the ONS 15454 M2 Shelf
DLP-G590 Mount the ONS 15454 M2 Shelf on the Wall