• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
• Wire wrapper
• Wire cutters
• Wire strippers
• Crimp tool
• Fuse panel
• Ground cable 13.3-mm² (#6 AWG) stranded. The PIDs of the power cables
are listed in Table 30: PIDs for AC Power Cables, on page 244.
Tools/Equipment
• NTP-G266 Install the ONS 15454 M2 Shelf, on page 194.
• Connect the chassis to the office ground. For detailed instructions on how
to ground the chassis, refer to the Electrostatic Discharge and Grounding
Guide for Cisco CPT and Cisco ONS Platforms .
• NTP-G270 Open and Remove the Standard Door of the ONS 15454 M2
Shelf, on page 218.
• NTP-G267 Install the Power Module in the ONS 15454 M2 Shelf, on page
230.
Prerequisite Procedures
RequiredRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
This product is intended for use on the TN and TT power systems.
Note
When installing or replacing the unit, the ground connection must always be made first and disconnected
last. Statement 1046
Warning
This equipment shall be connected to AC mains provided with a surge protective device (SPD) at the
service equipment complying with NFPA 70, the National Electrical Code (NEC). Statement 7012
Warning
The ONS 15454 M2 relies on the protective devices in the building installation to protect against short circuit,
overcurrent and ground faults. Ensure that the protective devices are properly rated and comply with national
and local codes.
Caution
Not more than 7 feet (2 m) of the power supply cable should be exposed between the equipment and the fiber
storage tray.
Note
Cisco ONS 15454 Hardware Installation Guide
242
Installing the ONS 15454 M2 Shelf
DLP-G596 Connect Office Power (AC) to the ONS 15454 M2 Shelf