Figure 211: Mounting the Bracket with Air Deflectors (Front-to-Side) on the ONS 15454 M6 Shelf for ETSI Rack Configuration
Step 2 Align the screw holes on the right front air deflector with the screw holes on the right side of the chassis.
Step 3 Insert M4 pan-head screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 4 Place the mounting bracket flush in the middle or front position of the right front air deflector (see Diagram
1 of Figure 212: Mounting the Bracket with Air Deflectors (Front-to-Side) on the ONS 15454 M6 Shelf for
ETSI Rack Configuration - Middle Position, on page 315 or Figure 213: Mounting the Bracket with Air
Deflectors (Front-to-Side) on the ONS 15454 M6 Shelf for ETSI Rack Configuration - Front Position, on
page 315).
Step 5 Align the screw holes on the mounting bracket with the screw holes on the right front air deflector .
Step 6 Insert M4 flat-head screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 7 Place the mounting bracket flush in the middle or front position on the left side of the chassis (see Diagram
2 of Figure 212: Mounting the Bracket with Air Deflectors (Front-to-Side) on the ONS 15454 M6 Shelf for
ETSI Rack Configuration - Middle Position, on page 315 or Figure 213: Mounting the Bracket with Air
Deflectors (Front-to-Side) on the ONS 15454 M6 Shelf for ETSI Rack Configuration - Front Position, on
page 315).
Step 8 Align the screw holes on the mounting bracket with the screw holes on the left side of the chassis.
Step 9 Insert M4 pan-head screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Cisco ONS 15454 Hardware Installation Guide
314
Installing the ONS 15454 M6 Shelf
DLP-G821 Mounting the Bracket with Air Deflectors (Front-to-Side) on the ONS 15454 M6 Shelf for ETSI Rack Configuration