NTP-G272 Replace the Fan-Tray Assembly of the ONS 15454 M2
Shelf Assembly
This procedure replaces the fan-tray assembly of the ONS 15454 M2 shelf
assembly.
Purpose
Small slot-head screwdriverTools/Equipment
NTP-G268 Install the Fan-Tray Assembly in the ONS 15454 M2 Shelf, on page
235
Prerequisite Procedures
RequiredRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
Do not force a fan-tray assembly into place. Doing so can damage either the connectors on the fan tray or the
connectors on the back panel of the shelf assembly, or both.
Caution
The estimated time required to change a fan-tray assembly is 2 minutes.
Note
Procedure
Step 1 Loosen the screw on the fan-tray assembly (see the following figure).
Figure 300: Fan-Tray Assembly installed in the ONS 15454 M2 Shelf Assembly
Cisco ONS 15454 Hardware Installation Guide
456
Maintaining the ONS 15454 M12 (ANSI and ETSI), ONS 15454 M2 and ONS 15454 M6 Shelf
NTP-G272 Replace the Fan-Tray Assembly of the ONS 15454 M2 Shelf Assembly