DMM-0200 Product User Guide
159 Swanson Road
Boxborough, MA 01719
Tel: 508-475-3400
Email: sales@dovermotion.com
Specifications for Power, Communications, and Environment
Electrical Power
The DMM-0200 requires a main power source, as specified in Table 2. Ensure that the AC power source is
easily accessible.
Table 2 Specifications for Electrical power
Specification
Voltage
90-264VAC ± 10%
Frequency
47-63 Hz
Current (at nominal voltage, 110VAC)
Typical, maximum, inrush
surge: No more than 11 amps.
Electrical receptacle
The DMM-0200 requires a NEMA 5-15 receptacle in North America. The electrical receptacle must be located
within 2.5 meters (approx. 8 feet) of the power cord input on the system.
Note: The electrical receptacle must have a dedicated 1.2kVA power line and ground.
Grounding
Certain types of electrical noise are greatly exaggerated by poor or improper electrical ground connections. To
prevent these problems, it is desirable to have a dedicated circuit and ground for use by the DMM-0400.
Note: For grounding wiring, the DMM-0200 uses internal AC ground connections with
green/yellow 16AWG wiring.
Warning: Do not connect the DMM-0200 to the same dedicated line and ground that is
used to power a device with a high current.
Warning: Use qualified personnel for installation of all electrical fixtures, and ensure
that all installations follow local bylaws.