EasyManua.ls Logo

Dräger Cato - Gas Delivery; Pipelinie Gas Supply; Reserve Gas Cylinders (Optional); Water Traps

Dräger Cato
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Water traps
1 Water traps are recommended in both the inspiratory
and the expiratory lines during prolonged anaesthesia,
low-flow anaesthesia and when using humidified
breathing gas.
Water traps must be fitted at the lowest point in the
hose and hang downwards.
Check regularly and drain if necessary.
Observe hygiene regulations –
risk of infection!
The hose system remains sealed. The container must
be replaced securely!
»Tips on reducing condensation« on page 136.
Reserve gas cylinders (optional)
Open cylinder valves.
Check and tick off:
Pressure indicator on O2 cylinder exceeds 50 bar? –
Pressure indicator on N2O cylinder exceeds 30 bar? –
Replace cylinders if not.
Close cylinder valves!
Pipelinie gas supply
Have connectors been pressed right into the wall
sockets for O2, AIR and N2O (not in holding
position!)?
Check and tick off:
2 Pointers of all three pressure indicators are in the
green range.
Gas delivery
3 Switch over to AIR.
4 Open O2 and AIR delivery valves until more than
9 L/min are indicated!
5 Open N2O delivery valve completely.
Check and tick off:
Does N2O measuring tube indicate 0?
3 Switch over to N2O.
Check and tick off:
Does N2O measuring tube indicate more than 9 L/min?
Does AIR measuring tube indicate 0?
24
Preparing for use
Checking readiness for operation with checklist
Water traps, Reserve gas cylinders
Pipelinie gas supply, Gas delivery
G
A
S
1
1
3
2
445
[
0382897000837224

Table of Contents

Related product manuals