7.7.5. Replacement
The replacement function provides different methods to calculate flow (Q). This option is applied in case of sensor failure or if
calculation of Q is required below or above preset min. and max. limit values for velocity, water level or signal strength.
Replacement
Behavior of replacement function
Setting Description
Waterlevel
below sensor
> Tick checkbox if no measurement is possible due to too low water level for proper
measurement.
Sensor failure
> Tick checkbox in case of sensor failure.
Velocity > Tick checkbox to activate replacement function, if current measurement value exceeds or
falls below the defined limit for flow velocity.
> Enter velocity limit value.
less = replacement function is activated if current measurement value falls below the defined
limit value.
greater = replacement function is activated if current measurement value exceeds the defined
limit value.
Waterlevel > Tick checkbox to activate replacement function if current measurement value exceeds or
falls below the defined limit for water level.
> Enter water level limit value.
less = replacement function is activated if current measurement value falls below the defined
limit value.
greater = replacement function is activated if current measurement value exceeds the defined
limit value.
Programming
Page 57 March 2021 HYB-UM-03155-EN-03