4 PKE-SWD-32, interface for motor-starter combination with PKE PKE12/32
4.6 Exchange of modules
108 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
4.6 Exchange of modules
After replacement of the modules and connection of the voltage the configu-
ration button must be pressed. When this is done, the new module will be
assigned an address.
4.7 Device Status
The individual SmartWire-DT modules indicate their device status with the
aid of a diagnosis LED. The diagnostics LED can have the following states:
Table 9: Diagnostic messages of the SmartWire-DT status LED
4.8 Parameterization
Depending on the coordinator being used, the module's parameters will
need to be configured in the programming system or in the SWD-Assist plan-
ning and commissioning program.
DANGER
The exchange of the SmartWire-DT module PKE-SWD-32 must
only be carried out with the supply switched off.
ACHTUNG
The order of the SmartWire-DT units must not be altered.
DANGER
The exchange of the motor starter or contactor must only be
carried out after the complete system SmartWire-DT is
switched off.
Designation Color State Message
Ready Orange Continuous light Switching command for contactor via SmartWire-DT
Flashing Communication to the PKE is interrupted, switch command for
contact is present via SmartWire-DT
Green Continuous light Device is operating error-free.
Flashing (1 Hz) Addressing process in progress
after gateway power On
after actuation of the configuration button on the gateway
Module not in current configuration
invalid type
Flashing (3 Hz) Incorrect manual/automatic switch setting
Communication to PKE is interrupted