2 I/O modules EU5E-SWD…
2.13 Analog module EU5E-SWD-2A2A
SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 55
2.13.4 Installation
Figure 23: Connecting inputs and supply of module EU5E-SWD-2A2A
â–¶ Connect the sensors to the corresponding inputs I0 to I1.
â–¶ Connect the actuators to the corresponding outputs Q0 to Q1.
â–¶ Connect the 24 V power supply for the card.
2.13.5 Parameterization
With the programming system’s control configurator, users can define the
sensor/actuator model, measured value refresh rate and averaging.
This setting applies to all analog inputs. The specified value is the refresh
time for the SmartWire-DT network. An averaging function that smooths
input signal fluctuations can be activated separately.
2.13.6 Fieldbus-specific characteristics
Field bus CANopen
U/I
0 V
24 V DC
24 V
0 V
+
U/I
+
+
+
I0–
I1–
I1+
I0+
Q0–
Q1–
Q1+
Q0+
Parameter Setting options Basic Setting
Sensor type I0 Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)
Sensor type I1
Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)
Actuator model Q0
Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)
Actuator model Q1
Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)
Parameter
Value (reading refresh rate) Averaging
On (default) Off
Reading refresh rate 20 ms 1
100 ms (default setting) 5 measurement cycles
200 ms 10 measurement cycles
500 ms 25 measurement cycles