2 I/O modules EU5E-SWD…
2.14 Analog modules EU5E-SWD-4PT and EU5E-SWD-4PT-2
SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 63
Structure of parameter byte 2:
2.14.7 Programming
The module has an input byte for SmartWire-DT status and four words for
the temperature inputs.
2.14.7.1 Input points
Byte 0:
Bit Function Configuration
0, 1 Measurement display Bit 1
0
0
1
Bit 0
0
1
0
= degrees Celsius
= degrees Fahrenheit
= Binary value
2, 3
Reading refresh rate Bit 3
0
0
1
1
Bit 2
0
1
0
1
= 0.25 s
= 1 s
= 2.5 s
= 10 s
4
reserved 0
5
reserved 0
6 reserved 0
7 reserved 0
Bold values indicate the default settings.
76543210
SUBST PRSNT DIAG
Bit
Designation Description
0 Not used
1
Not used
2
Not used
3
Not used
4
DIAG 0: no diagnostic alarm
1: Diagnostic alarm
5
Not used
6
PRSNT 0: Module not available
1: Module available
7
SUBST 0: Configured module present
1: universal module M22-SWD-
NOP(C) present