2 I/O modules EU5E-SWD…
2.14 Analog modules EU5E-SWD-4PT and EU5E-SWD-4PT-2
62 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
Fieldbus EtherCAT
Please note the general information for configuring parameters Section
12, „Using SWD modules with the EtherCAT field bus“, page 247, particu-
larly
Section , „Device options“, page 247.
Defining the sensor type and the measuring settings:
Device index: sub-index 22
Parameter data length: 0x03
Structure of parameter byte 1:
The CANopen field bus transmits data event-controlled when-
ever the reading changes.
Reducing the reading refresh rate, for example to 50 ms, can
increase data traffic on the field bus.
Bit Function Configuration
0, 1 Sensor selection
Input 1
Bit 1
0
0
1
1
Bit 0
0
1
0
1
= not used
= PT100
= PT1000
= NI1000
2, 3
Sensor selection
Input 2
Bit 3
0
0
1
1
Bit 2
0
1
0
1
= not used
= PT100
= PT1000
= NI1000
4, 5
Sensor selection
Input 3
Bit 5
0
0
1
1
Bit 4
0
1
0
1
= not used
= PT100
= PT1000
= NI1000
6, 7
Sensor selection
Input 4
Bit 7
0
0
1
1
Bit 6
0
1
0
1
= not used
= PT100
= PT1000
= NI1000
Bold values indicate the default settings.