EasyManua.ls Logo

Eaton SmartWire-DT SWD Series - DOL Starter

Eaton SmartWire-DT SWD Series
293 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Switching on DIL-SWD-32-001, DIL-SWD-32-002 contactors
3.3 Engineering
68 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
3.3.1 DOL starter
The DOL starter is assembled from a PKZM0 and a contactor DILM7 to
DILM32. The SmartWire module for DILM is mounted on the contactor. The
SmartWire-DT module for DILM is mounted on the contactor.
ATTENTION
The sum of the pull-in power of the simultaneously tripping con-
tactors and the sum of the holding power of the tripped contac-
tors for each SmartWire-DT network must not exceed 72 W. If
required, an additional power feeder module (EU5C-SWD-PF1-1,
EU5C-SWD-PF-2) must be used
( Chapter 1 “EU5C-SWD-PF1-1, EU5C-SWD-PF2-1 power
modules”, page 15)
The DIL modules draw their energy for the communication elec-
tronics and for activation of the LEDs and of the auxiliary con-
tacts from the SmartWire-DT network supply. Please take into
consideration the total power consumption of your SmartWire-
DT network and, if necessary, plan for an additional feeder mod-
ule EU5C-SWD-PF2-1.
For data for the current requirement please refer to the table in
the appendix on Page 253.
DIL-SWD-32-001 DIL-SWD-32-002
Figure 27: Connections of the SmartWire-DT module
DIL-SWD-32-001 or DIL-SWD-32-002 for DILM
a Connection of SmartWire-DT external device plug
b Mechanical switching position indicator
c Diagnostics LED
d Catch slider
e Connection pins
f Adjusting slide for contactor size
g Terminal X0-X1-X2
h Terminal, electrical enable X3-X4
i Selector switch 1-0-A
a
c
b
d
g
f
e
h
a
c
b
d
g
f
e
h
i

Table of Contents

Related product manuals