EasyManuals Logo

Eaton SmartWire-DT SWD Series User Manual

Eaton SmartWire-DT SWD Series
293 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #120 background imageLoading...
Page #120 background image
4 PKE-SWD-32, interface for motor-starter combination with PKE PKE12/32
4.9 Programming
116 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
4.9.2.1 ZMR operating mode manual
In "manual" ZMR operating mode, the retriggering of the contactor must be
acknowledged beforehand. The necessity of an acknowledgement is indi-
cated by the ACKR bit field (input byte 1, Bit 7). The bit value "1" indicates
that an overload with manual ZMR function was detected. Bit value "0" indi-
cates that no overload is present and that an acknowledgement has already
taken place. The "manual" ZMR operating mode is activated by sending the
value "0" in bit field ZMR M/A (output byte 0, Bit 3).
ï¿«
In the event of a phase unbalance and activated ZMR function,
the value of the thermal motor image is raised from 100 % to
110 % after a trip.
The switched off contactor's availability to reclose is restored
when the value falls below 100 %.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton SmartWire-DT SWD Series and is the answer not in the manual?

Eaton SmartWire-DT SWD Series Specifications

General IconGeneral
BrandEaton
ModelSmartWire-DT SWD Series
CategoryControl Unit
LanguageEnglish

Related product manuals