13 Appendix
13.7 Technical data
282 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
Surge (IEC/EN 61131-2:2008, Level 1) Figure 91: Performance criterion B
(tested with 0.5kV/
0.5kV)
Radiated RFI
(IEC/EN 61131-2:2008, Level 3)
V
10
Ambient climatic conditions
Operating ambient temperature (IEC 60068-2) °C -30 up to +60
Condensation
Must be prevented with suitable measures
Storage °C
-30 up to +85
Relative humidity, non-condensing (IEC/EN
60068-2-30)
%
5 – 95
SmartWire-DT interface
Module type SmartWire-DT module (slave)
Baud rate setting
Automatic
Status SmartWire-DT LED
Green
Connection
Pin contact, 8 pole;
Connector: blade terminal SWD4-8MF2
Device supply voltage
SWD module
U
SWD
V DC,
(%)
14.5 (±3)
Current consumption at U
SWD
ï¿« Page 253
Potential isolation
From supply voltage U
AUX
From 24 VDC external supply voltage
From the light/acoustic modules
Yes
Supply voltage AUX
Rated operating voltage U
e
VDC,
(%)
24 (-15/+20)
Residual ripple %
–
max. current consumption A
0.9 1.5
Protection against polarity reversal
Yes
Potential isolation
From 24 VDC external auxiliary power
From device supply voltage for SmartWire-DT
modules U
SWD
Yes
From the light/acoustic modules
no
External supply voltage 24 V DC
Connection type Push-In
solid
mm2
0.25 – 1.5
flexible with ferrule
1) mm2
0.25 – 1.5
UL/CSA solid or stranded AWG
24 – 16
Rated operating voltage U
e
VDC,
(%)
24 (-15/+20)
Residual ripple %
–
max. current consumption A
0.9 1.5
Protection against polarity reversal
Yes
Potential isolation
SL4-SWD SL7-SWD