2 I/O modules EU5E-SWD…
2.7 Digital module EU5E-SWD-4DX
SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 31
2.7.7.1 Input points
Byte 0:
Byte 1:
2.7.7.2 Diagnostics
In case of diagnosis, the module reports the following fault cause (bit 4 in
input byte 0 is set):
76543210
SUBST PRSNT – DIAG – – – –
Bit
Designation Description
0 Not used –
1
Not used –
2
Not used –
3
Not used –
4
DIAG 0: no diagnostic alarm
1: Diagnostic alarm
5
Not used –
6
PRSNT 0: Module not available
1: Module available
7
SUBST 0: Configured module present
1: universal module M22-SWD-
NOP(C) present
76543210
––––I3I2I1I0
Bit
Designation Description
0 I0 Status input I0
1
I1 Status input I1
2
I2 Status input I2
3
I3 Status input I3
4
Not used –
5
Not used –
6
Not used –
7
Not used –
Value Description
0x13 Short-circuit/overload at supply voltage