2 I/O modules EU5E-SWD…
2.11 Digital module EU5E-SWD-X8D
48 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
2.11.7.1 Input points
Byte 0:
2.11.7.2 Outputs
Byte 0:
2.11.7.3 Diagnostics
In case of diagnosis, the module reports the following fault cause (bit 4 in
input byte 0 is set):
76543210
SUBST PRSNT – DIAG – – – –
Bit
Designation Description
0 Not used –
1
Not used –
2
Not used –
3
Not used –
4
DIAG 0: no diagnostic alarm
1: Diagnostic alarm
5
Not used –
6
PRSNT 0: Module not available
1: Module available
7
SUBST 0: Configured module present
1: universal module M22-SWD-NOP(C) present
76543210
Q7 Q6 Q5 Q4 Q3 Q2 Q1 Q0
Bit
Designation Description
0 Q0 Actuation output Q0
1
Q1 Actuation output Q1
2
Q2 Actuation output Q2
3
Q3 Actuation output Q3
4
Q4 Actuation output Q4
5
Q5 Actuation output Q5
6
Q6 Actuation output Q6
7
Q7 Actuation output Q7
Value Description
0x13 Short-circuit/overload on at least one output