2 I/O modules EU5E-SWD…
2.12 Analog module EU5E-SWD-4AX
SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 51
The module is parameterized through its associated parameter byte in the
control configurator.
For values other than the default, change these values as shown below.
Structure of parameter byte 1:
Bit Function Configuration
0 Sensor selection
Input 1
0 = Voltage
1 = Current
1
Sensor selection
Input 2
0 = Voltage
1 = Current
2
Sensor selection
Input 3
0 = Voltage
1 = Current
3
Sensor selection
Input 4
0 = Voltage
1 = Current
4 , 5
Reading refresh rate Bit 5
0
0
1
1
Bit 4
0
1
0
1
= 20 ms
= 100 ms
= 200 ms
= 500 ms
6
Mean value 0 = off
1 = on
7
reserved 0
Bold values indicate the default settings.
ï¿«
The CANopen field bus transmits data event-controlled when-
ever the reading changes. Reducing the reading refresh rate, for
example to 20 ms, can increase data traffic on the field bus.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton SmartWire-DT SWD Series and is the answer not in the manual?

Eaton SmartWire-DT SWD Series Specifications

General IconGeneral
BrandEaton
ModelSmartWire-DT SWD Series
CategoryControl Unit
LanguageEnglish

Related product manuals