4 PKE-SWD-32, interface for motor-starter combination with PKE PKE12/32
4.3 Engineering
88 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
Table 8: Wattage/ and current consumption of the contactor coils at a voltage of 24 V DC
Contactor
Pull-in power
[W]
Pick-up current
at 24 V DC [mA]
Sealing
consumption
[W]
Holding current
at 24 V DC
[mA]
DILA, DILM7 3 125 3 125
DILM9 - DILM15
4.5 188 4.5 188
DILM17 - DILM38
12 500 0.5 21
ACHTUNG
The sum of the pull-in power of the simultaneously tripping con-
tactors and the sum of the holding power of the tripped contac-
tors for each SmartWire-DT network must not exceed 72 W. If
required, an additional power feeder module (EU5C-SWD-PF1-1,
EU5C-SWD-PF-2) must be used
(ï¿« Chapter 1, "EU5C-SWD-PF1-1, EU5C-SWD-PF2-1 power
modules", page 15).
ï¿«
The PKE-SWD-32 draws its energy for the communication elec-
tronics and for controlling the LED from the SmartWire-DT net-
work supply.
Please take into consideration the total power consumption of
your SmartWire-DT network and, if necessary, plan for an addi-
tional feeder module EU5C-SWD-PF2-1.
ï¿«
For data for the current requirement please refer to the table in
the appendix on Page 254.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton SmartWire-DT SWD Series and is the answer not in the manual?

Eaton SmartWire-DT SWD Series Specifications

General IconGeneral
BrandEaton
ModelSmartWire-DT SWD Series
CategoryControl Unit
LanguageEnglish

Related product manuals