EasyManua.ls Logo

Ecotech Serinus 30 - Interferents

Ecotech Serinus 30
254 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TÜV Rheinland Energie und Umwelt GmbH
Luftreinhaltung
Seite 96 von 253
Report on the performance testing of the Serinus 30 ambient air quality
monitoring system manufactured by Ecotech Pty Ltd measuring CO, Report
no.: 936/21221977/D_EN
EP_Ecotech_Serinus30_en.docx
7.1 8.4.11 Interferents
Interferents at zero and at a concentration c
t
(at a level of the 8-hour limit =
8.6 µmol/mol for CO). The highest permissible response to the interfering compo-
nents CO
2
, NO, and N
2
O shall not exceed 5.0 µmol/mol (i.e. 5.8 mg/m
3
) respectively
and 10.0 µmol/mol (i.e. 11.6 mg/m
3
) for H
2
O.
7.2 Test procedure
The analyser response to certain interferents, which are to be expected to be present in am-
bient air, shall be tested. The interferents can give a positive or negative response. The test
shall be performed at zero and at a test concentration (c
t
) of carbon monoxide similar to the
8-hour limit value (8.6 µmol/mol for CO).
The concentration of the mixtures of the test gases with the interferent shall have an ex-
panded uncertainty of 5 % and shall be traceable to nationally accepted standards. The in-
terferents to be tested and their respective concentrations are given in Table 22. The influ-
ence of each interferent shall be determined separately. A correction on the concentration of
the measurand shall be made for the dilution effect due to addition of an interferent (e.g. wa-
ter vapour).
After adjustment of the analyser at zero and span level, the analyser shall be fed with a mix-
ture of zero gas and the interferent to be investigated with the concentration as given in Ta-
ble 22. With this mixture, one independent measurement followed by two individual meas-
urements shall be carried out. This procedure shall be repeated with a mixture of the meas-
urand at concentration c
t
and the interferent to be investigated. The influence quantities at
zero and concentration c
t
are calculated from:
zz
xX =
int,
tctct
cxX =
int,
where
z
X
int,
is the influence quantity of the interferent at zero, in µmol/mol;
z
x
is the average of the measurements at zero, in µmol/mol;
ct
X
int,
is the influence quantity of the interferent at concentration c
t
, in µmol/mol;
ct
x
is the average of the measurements of CO at concentration c
t
, in µmol/mol;
t
c
is the carbon monoxide test gas concentration at the level of the 8-hour limit val-
ue, in µmol/mol.
The influence quantities of the interferents shall comply with the performance criteria as stat-
ed above, both at zero and at concentration c
t
.
7.3 Testing
The test was performed in accordance with the requirements on testing as stipulated in DIN
EN 14626. The systems were adjusted to zero concentration and to the concentration c
t
(ap-
prox. 8.6 µmol/mol). Zero and test gas with various interferents were then applied. Inter-
ferents and their respective concentrations used during testing are provided in Table 22.

Table of Contents

Related product manuals