Operating menu and parameter description iTEMP TMT162
110 Endress+Hauser
Burst trigger mode
Navigation Expert → Communication → Burst configuration → Burst trigger mode
Prerequisite: This parameter can only be selected if the Burst mode option is enabled.
Description Use this function to select the event that triggers burst message X.
Continuous:
The message is triggered in a time-controlled manner, at least observing the time
interval defined in the Min. update period parameter.
Window:
The message is triggered if the specified measured value has changed by the value
defined in the Burst trigger level X parameter.
Rising:
The message is triggered if the specified measured value exceeds the value in the
Burst trigger level X parameter.
Falling:
The message is triggered if the specified measured value falls below the value in
the
Burst trigger level X parameter.
On change:
The message is triggered if a measured value of the message changes.
User entry Continuous
Window
Rising
Falling
On change
Factory setting Continuous
Burst trigger level
Navigation Expert → Communication → Burst configuration → Burst trigger level
Prerequisite: This parameter can only be selected if the Burst mode option is enabled.
Description Use this function to enter the value which, together with the trigger mode, determines the
time of burst message 1. This value determines the time of the message.
User entry -1.0e
+20
to +1.0e
+20
Factory setting -10.000
Min. update period
Navigation Expert → Communication → Burst configuration → Min. update period