Operating menu and parameter description iTEMP TMT162
108 Endress+Hauser
Description Use this function to assign a measured variable to the quaternary (fourth) HART value
(QV).
Options See Assign current output (PV) parameter, → 69
Factory setting Sensor 1
QV
Navigation Expert → Communication → HART output→ QV
Description Use this function to display the quaternary HART value
"Burst configuration" submenu
Up to 3 burst modes can be configured.
Burst mode
Navigation Expert → Communication → Burst configuration → Burst mode
Description Activation of the HART burst mode for burst message X. Message 1 has the highest
priority, message 2 the second-highest priority, etc.
User entry • Off
The device only sends data to the bus at the request of a HART master
• On
The device regularly sends data to the bus without being requested to do so.
Factory setting Off
Burst command
Navigation Expert → Communication → Burst configuration → Burst command
Prerequisite: This parameter can only be selected if the Burst mode option is enabled.
Description Use this function to select the command whose answer is sent to the HART master in the
activated burst mode.