Operating menu and parameter description iTEMP TMT162
94 Endress+Hauser
Sensor n lower limit
Navigation Expert → Sensor → Sensor n → Sensor n lower limit
Description Displays the minimum physical full scale value.
Sensor n upper limit
Navigation Expert → Sensor → Sensor n → Sensor n upper limit
Description Displays the maximum physical full scale value.
Sensor serial number
Navigation Expert → Sensor → Sensor n → Serial no. sensor
Description Use this function to enter the serial number of the connected sensor.
User entry String with up to 12 characters consisting of numbers and/or text
Factory setting " " (no text)
"Sensor trimming" submenu
Sensor error adjustment (sensor trimming)
Sensor trimming is used to adapt the actual sensor signal to the linearization of the
selected sensor type stored in the transmitter. Compared to sensor transmitter matching,
sensor trimming only takes place at the start and end value and does not achieve the same
level of accuracy.
Sensor trimming does not adapt the measuring range. It is used to adapt the sensor
signal to the linearization stored in the transmitter.
Procedure
1. Start
ß
2. Set the Sensor trimming parameter to the Customer-specific setting.
ß
3. Using a water/oil bath, bring the sensor connected to the transmitter to a known and stable temperature. A
temperature which is close to the set start of the measuring range is recommended.
ß