Operating menu and parameter description iTEMP TMT162
78 Endress+Hauser
Factory setting Min.
Failure current
Navigation Setup → Advanced setup → Current output→ Failure current
Expert → Output → Failure current
Prerequisite The Max.
option is enabled in the Failure mode parameter.
Description Use this function to set the value the current output adopts in an alarm condition.
User entry 21.5 to 23.0 mA
Factory setting 22.5
Current trimming 4 mA
Navigation Setup → Advanced setup → Current output→ Current trimming 4 mA
Expert → Output → Current trimming 4 mA
Description Use this function to set the correction value for the current output at the start of the
measuring range at 4 mA.→  76
User entry 3.85 to 4.15
mA
Factory setting 4 mA
Current trimming 20 mA
Navigation Setup → Advanced setup → Current output→ Current trimming 20 mA
Expert → Output → Current trimming 20 mA
Description Use this function to set the correction value for the current output at the end of the
measuring range at 20 mA.→  76
User entry 19.850 to
20.15 mA
Factory setting 20.000 mA
Reset trim