Operating menu and parameter description iTEMP TMT162
92 Endress+Hauser
Additional information The current output reacts with an exponential delay to fluctuations in the measured value.
The time constant of this delay is specified by this parameter. If a low time constant is
entered, the current output follows the measured value quickly. On the other hand, if a
high time constant is entered, the current output reaction is delayed.
Alarm delay
Navigation Expert → System → Alarm delay
Description Use this function to set the delay time during which a diagnostics signal is suppressed
before it is output.
User entry 0 to 5 s
Factory setting 2 s
Mains filter
Navigation Expert → System → Mains filter
Description Use this function to select the mains filter for A/D conversion.
User entry 50 Hz
60 Hz
Factory setting 50 Hz
"Display" submenu
Detailed information →  79
"Administration" submenu
Detailed information
→  82
14.3.2 "Sensor" submenu
Measurement channels
Navigation Expert → Sensors → Measurement channels
Description Displays information on the connected and configured measurement channels
User entry Not initiated
1-channel device
2-channel device